Features & Benefits
- 3 LEDs provide basic diagnostic information
- Single or multiple trials for ignition before lockout
- Designed for easy mounting on a 4 x 4 junction
- Selectable ignition timing 4-15 seconds
- Selectable pre-purge timing 1-240 seconds
- Selectable relight or recycle operation on loss of flame
- The microprocessor is checked for proper operation before each cycle
- Checks combustion air proving switch contacts on 7590C and D models
- Gas valve relay check on each cycle
- Available model (7590C) with manual reset button and non-volatile lockout
- Communication Port links new alarm module and future products
- For use on natural or LP gas
- Provides reliable proof of flame using flame rectification
The standard 7590 is designed for use on applications below 400,000 BTUs. For applications above 400,000 BTUs, contact Beckett’s Engineering Group.
Outputs
-
- Main Valve Rating: 2.0 amps
- Motor Relay Rating: 7.4 amps (120 V)
- Igniter Relay Rating: 1.0 amp (120 V)
Approvals
-
- UL listing per ANSI Z21.20, UL372 and CSA C22.2 No. 199
Timings
-
- Ignition Timing: 4-15 seconds
- Pre-purge Timing: 1-240 seconds
- Inter-purge Timing: 90-300 seconds
Additional Ratings
-
- Minimum Flame Current Required: 1.0 µA
- Flame Failure Response Time: 0.8 seconds (maximum)
- Thermostat Voltage: 24 Vac (if used)
- Heat Anticipator Setting: 0.2 amps + gas valve current draw (control is not polarity sensitive)
Environmental Ratings
- Storage & Operating Ambient Temperature: -40°F to +175°F (-40°C to +79.4°C)